Detail of an installed ground screw

Ground screw testing in Axminster

Arrange ground screw testing in Axminster with JustBases as a service in its own right. We offer pull, compression and lateral tests for suitable trials and existing foundations, including screws fitted by another installer. The agreed programme measures the response under load and provides written evidence for the person assessing the foundation.

Tests for uplift, downward and sideways loads

A building can place different forces into its supports. Testing examines the response of selected screws to the loading specified for the project, recording movement alongside the force applied. It can help an assessor make a foundation decision using measured information.

The test directions below are separate choices, not a required bundle. The responsible designer or appointed assessor establishes the evidence needed, including test locations, loads and criteria. We agree a practical programme to carry out that work safely.

Pull testing

An upward load is applied to examine uplift resistance. The test records how the screw responds to that lifting action under the agreed conditions. Use it where the assessment requires evidence about upward forces at the selected support.

Learn more: Pull testing

Compression testing

A direct compression test pushes downwards and measures the resulting response. This provides downward-loading evidence. An agreed calculation of compression capacity from other testing is a different assessment, reported on its stated derived basis rather than as a direct physical measurement.

Learn more: Compression testing

Lateral testing

The loading acts sideways to examine lateral response. The direction of force, application height and connection need to represent the specified check. Its findings concern that sideways arrangement rather than automatically providing an uplift or compression result.

Learn more: Lateral testing

Ground screw testing prices

The guide below gives the main test prices. We confirm a quotation for the programme you commission, including the chosen methods and number of positions, safe setup, attendance and reporting. Tell us about any agreed calculations or particular evidence requested so those requirements can be priced.

Installation torque monitoring records resistance to turning while the screw is driven into the ground. A specialist torsional test applies a separate twisting load to examine the response. Both services are priced on application and individually scoped: neither is automatically included when you arrange pull, compression or lateral testing.

Local guide prices start with our Ringwood prices, adding 0.1% for each one-way road mile to the town, then rounding up to a whole pound. Your written quotation confirms the price for your site and agreed work.

Installation torque monitoring
Price on application
Specialist torsional load test
Price on application

Each additional test

Each extra charge applies to an additional test of the same type, at the same location on the same day. The first test of each type is priced separately.

Pull test (tensile or uplift test)
£160 extra
Load test (compression test)
£320 extra
Lateral test (sideways load)
£155 extra

No VAT is added to the guide prices shown. Guide prices are subject to site conditions, access and the written quotation.

Explain the testing you need

You can begin with a short explanation of the foundation and its postcode. Say whether the screws are still proposed or already installed, and what prompted the request. We can then discuss the information needed to agree the tests; documents and photographs are optional at first contact.

Use this form, contact Craig through WhatsApp, or call 01202 039753. Testing can be quoted without an order for new screws or a building base.

Request your free quote

Give us your contact details and a short description of the testing you need. You can ask before the technical requirements are complete.

Your enquiry

Ground screw testing in Axminster

Please provide either an email address or a phone number.

Add site photos, video or a drawing (optional)

Upload up to 5 photos or a short video of your site to help us provide an accurate quote.

0/5 files. JPG, PNG, WebP, PDF, MP4, MOV accepted — up to 100MB each.

Free, no-obligation quote. Your details are used to respond to this enquiry; see our privacy policy.

Planning the test and recording results

We establish the required evidence and the safe test arrangement before the visit. The following stages connect the assessment request with the work carried out and the record supplied afterwards.

Define the testing programme

Identify the assessment question and available foundation details. Agree with the responsible assessor which screws and loading directions are required, together with the loading sequence, acceptance and stopping criteria, and reporting.

Settle preparation and safe access

Establish the means of reaching and connecting to the screws. Assess the loading arrangement and any structure already attached, then agree the preparation and competent support or access work needed before testing.

Apply loads and measure movement

Carry out the specified test sequence, recording applied loads and the corresponding movement. The selected positions and relevant conditions or observations are identified so the results can be understood in their proper context.

Issue the agreed record

Provide the written results and agreed calculations for the assessment. The responsible designer or other appointed assessor reviews the evidence against the requirements and decides how it informs the foundation work.

Trial screws and existing foundations

An existing foundation may have incomplete records. Explain what you know about the screws and why you need them checked, and send the information already available. We can establish which missing details matter to the proposed test and its interpretation before agreeing attendance. Another installer having fitted the supports does not prevent a standalone enquiry.

Access for testing must preserve the support of anything already built. A covered screw head may require agreed preparation, but first show what can be seen without taking the structure apart. The test connection, existing loads and any temporary support need a competent plan; dismantling a loaded frame is not preparation to undertake simply to obtain a quote.

For a proposed foundation, a trial should be commissioned at a stage when its findings can still influence the design. The assessor selects relevant screw details and locations for the question being investigated. Agree how trial supply, installation and testing fit together, with time to review the findings before proceeding with the remaining foundation.

Understanding the report

The written findings answer the agreed testing brief. They identify the test positions and what was done there, with the recorded loading and movement. Use those details when discussing the outcome with your assessor, particularly if more than one method or location forms part of the programme.

A calculated compression capacity and a measured downward response carry different evidence. Where pull-test results support a compression calculation, the method must be agreed and applicable to the screw and project, with its assumptions explained. If the requirement is for a direct downward test, that physical measurement needs to be commissioned.

The report and agreed project calculations contribute to the foundation assessment. They do not provide a design for every part of the building or automatically grant approval. Identify any additional professional assessment or certification needed when planning the work, and confirm that the intended reviewer will receive the evidence they require.

Arranging a test in the Axminster area

Consider when the result can be used as well as the preferred day of testing. If a construction decision depends on it, allow time for the test record to be reviewed before that work proceeds. Tell us which person is coordinating the programme so the agreed preparation and attendance can fit together.

To discuss the site, a clear address and photographs of the proposed testing area are helpful. Explain what is already built and how the positions are reached. We confirm the practical space and entry arrangements once the method and selected screws are understood, including any enabling work needed before the visit.

If your project also needs supports installed, Axminster ground screw installation explains the foundation and frame options. Our Axminster base services cover the other methods, and you can see where we work in Devon. You can enquire about testing alone.

Axminster and nearby testing locations

Send the purpose and postcode for a testing enquiry in Axminster or the communities below. We confirm whether the specified work, access and attendance can be arranged for the actual address.

Local requests include EX13 and adjoining EX14, EX12, DT7, DT6 and TA20 addresses, with travel and reporting included in the agreed quotation. A nearby location outside those districts can also be discussed.

  • Axminster areas: town centre, Castle Hill, Cloakham Lawns, Millwey Rise, Millbrook, Woodbury Park, Lea Combe, Foxhill, Sector Lane, Abbey Gate, Weycroft and Raymonds Hill.
  • All Saints and Membury: All Saints, Smallridge, Churchill, Alston, Waggs Plot, Membury, Rock, Furley, Webble Green and Longbridge.
  • Chardstock and Chard-side places: Chardstock, Tytherleigh, Bewley Down, Birchill, Burridge, Holy City, Tatworth, South Chard, Forton and Wambrook.
  • Kilmington and the adjoining villages: Kilmington, Dalwood, Stockland, Shute, Seaton Junction, Whitford, Musbury, Colyton, Colyford, Axmouth and Seaton.
  • Hawkchurch and nearby border places: Hawkchurch, Holditch, Thorncombe, Chard Junction and Forde Abbey.
  • Uplyme and neighbouring places: Uplyme, Yawl, Rousdon, Combpyne, Monkton Wyld, Wootton Fitzpaine, Marshwood, Charmouth and Lyme Regis.

Feedback on Craig’s earlier work

Feedback on Craig’s earlier groundwork and customer service.

"Craig and the team are absolutely fantastic. From courtesy, to standard of work, to tidiness — everything exceeded expectations. The job was arranged, booked and done extremely quickly and we are very happy with the results. Nothing was too much trouble, and communication was easy."
— Verified CustomerMyBuilder · SO · Cobble edge and gravel strip
"Craig and his crew were excellent from the first communication, quote, timing of work and quality of work. Highly recommended."
— Verified CustomerCheckatrade · BH20 · Garage base

Ground screw testing FAQs

You can ask about a suitable test before you have gathered every foundation record. The programme and its responsibilities are confirmed before booking.

Can I use JustBases for testing only?

Yes. You can request testing for suitable screws without buying our installation service, including an existing foundation fitted by another contractor. We need to establish that the screw, connection and site can be tested appropriately. Start with the location and why the evidence is needed.

At what point should I discuss a trial test?

Raise it while the foundation decisions it will inform are still open. A trial needs an agreed relationship to the proposed supports and the loads being investigated. Allow for its installation, the testing and the assessor's review before committing work that depends on the findings.

Can one load direction answer all the design questions?

The result describes the response to the loading applied. Uplift, compression and sideways forces are different loading cases, so the assessor identifies the evidence needed for each relevant requirement. We can arrange the specified methods together, but the testing programme should make clear which questions each one addresses.

What does the height of a lateral test affect?

A sideways force applied at a given height creates a bending action as well as a horizontal force. The specified height, direction and connection therefore matter to the assessment being made. Pass on those requirements when available so the loading arrangement can be planned for that check.

What if I do not know which screws are installed?

Say what is known and share any safe photographs, invoices, layout or installation records. We discuss whether identification or further information is needed to carry out and interpret the requested test. Measuring a load response does not by itself reveal all hidden product dimensions or installation details.

Must I uncover the screw heads before contacting you?

No. An enquiry can start with an explanation of what covers them and photographs of visible details. Access work may be necessary for the selected test, but its extent and any effect on the connected structure are assessed first. Keep structural members and loaded fixings in place until competent arrangements have been agreed.

Can the same result be used for other supports on the site?

That is for the responsible assessor to establish. The result concerns the tested screw, position and arrangement; its relevance elsewhere depends on the foundation and available evidence. The chosen locations and any additional checks should be specified to answer the project question rather than assuming all supports have been demonstrated by one test.

Who supplies the acceptance criteria?

The designer or other person appointed to assess the foundation defines what the test must demonstrate. That includes relevant loads and movement requirements. We settle the practical programme against that brief before attendance, so the measurements can be judged against requirements established for the project.

Can you recreate a missing installation-torque record later?

Monitoring records turning resistance during the driving operation, so a later load test is not the original installation record. Explain what information is missing and what the assessor needs to establish now. A separately agreed test may provide other useful evidence, but its method and meaning must be described accurately.

How is specialist torsional testing different?

It examines the response to a defined twisting action applied as a test, rather than observing resistance during installation. Tell us what has been requested so the product, connection and test method can be considered. Both specialist torsional testing and installation monitoring are price on application and only included when separately specified.

How is a compression calculation distinguished from a direct test?

The report states the calculation's basis and assumptions, using an agreed method applicable to the project. It is identified as derived information. In a direct compression test the screw is physically loaded downwards and its movement measured. Confirm which evidence your assessor requires when the work is commissioned.

Can I send the evidence request from my project team?

Please do. It can clarify the required measurements, report content and any calculations or further professional review. We agree which deliverables are within the testing quotation before the visit. The report supplies that evidence; certification or approval of the whole building is a separate responsibility.

Can a trial screw be left in the permanent foundation?

Its intended later use must be considered when the programme is planned. The test loading and resulting condition may affect suitability, so the responsible designer decides whether it can remain a support and what further checks or work are required. Agree that decision and any reinstatement rather than assuming a tested screw is ready for permanent loading.

What do you need before you can confirm attendance?

We agree the methods, positions, loading programme, criteria and reporting, together with a safe practical arrangement and site access. Any preparation by others needs to be ready for the visit. You can still begin much earlier with the project purpose and postcode; we explain the outstanding details as the enquiry develops.

What does each additional ground screw test cost?

At the same location on the same day, each additional compression test costs £320 extra, each additional pull, tensile or uplift test costs £160 extra, and each additional lateral test costs £155 extra. These fixed charges are for further tests of the same type. The first test of each type is priced separately, using the starting price for your location. The extra-test charges stay the same in every location.

Request a testing quote

Explain your Axminster testing requirement, or tell us what you need to find out. We can discuss the proposed work, establish the required information and provide a written scope and price.